ABB RELION SMU615 Technical Manual page 239

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
Parameter
Values (Range)
Event delay
0...10000
Vendor
Serial number
Model
8.1.7.2
DCXSWI Non group settings
Table 264: DCXSWI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Select timeout
10000...300000
Pulse length
10...60000
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
Operation timeout
10...60000
Identification
Table 265: DCXSWI Non group settings (Advanced)
Parameter
Values (Range)
Operation counter
0...10000
Adaptive pulse
0=False
1=True
Event delay
0...60000
Vendor
Serial number
Model
8.1.7.3
ESXSWI Non group settings
Table 266: ESXSWI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
Table continues on the next page
SMU615
Technical Manual
Unit
Step
ms
1
Unit
Step
ms
10000
ms
1
ms
1
Unit
Step
1
ms
1
Unit
Step
Control functions
Default
Description
200
Event delay of the
intermediate posi-
tion
0
External equipment
vendor
0
External equipment
serial number
0
External equipment
model
Default
Description
1=on
Operation mode
on/off
30000
Select timeout in
ms
100
Open and close
pulse length
4=sbo-with-en-
Select control mod-
hanced-security
el
30000
Timeout for nega-
tive termination
DCXSWI1 switch
Control Object
position
identification
Default
Description
0
Breaker operation
cycles
1=True
Stop in right posi-
tion
10000
Event delay of the
intermediate posi-
tion
0
External equipment
vendor
0
External equipment
serial number
0
External equipment
model
Default
Description
1=on
Operation mode
on/off
239