Measurement functions
7.1.8.3
Signals
CSMSQI Input signals
Table 234: CSMSQI Input signals
Name
I
0
I
1
I
2
7.1.8.4
Settings
CSMSQI Non group settings
Table 235: CSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Ps Seq A Hi high
0.00...40.00
Lim
Ps Seq A high limit
0.00...40.00
Ps Seq A low limit
0.00...40.00
Ps Seq A low low
0.00...40.00
Lim
Ps Seq A deadband 100...100000
Ng Seq A Hi high
0.00...40.00
Lim
Ng Seq A High limit 0.00...40.00
Ng Seq A low limit
0.00...40.00
Table continues on the next page
206
Type
SIGNAL
SIGNAL
SIGNAL
Unit
Step
xIn
1
xIn
1
xIn
1
xIn
1
1
xIn
1
xIn
1
xIn
1
Default
Description
0
Zero sequence cur-
rent
0
Positive sequence
current
0
Negative sequence
current
Default
1=on
1.40
1.20
0.00
0.00
2500
0.20
0.05
0.00
1MRS758407 C
Description
Operation Off / On
High alarm current
limit for positive
sequence current
High warning cur-
rent limit for pos-
itive sequence cur-
rent
Low warning cur-
rent limit for pos-
itive sequence cur-
rent
Low alarm current
limit for positive
sequence current
Deadband configu-
ration value for
positive sequence
current for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
High alarm current
limit for negative
sequence current
High warning cur-
rent limit for neg-
ative sequence cur-
rent
Low warning cur-
rent limit for neg-
ative sequence cur-
rent
SMU615
Technical Manual