Basic functions
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
setting. Both timers use the same setting parameter.
Figure 62: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
TPSGAPC Input signals
Table 120: TPSGAPC Input signals
Name
IN1
IN2
TPSGAPC Output signals
Table 121: TPSGAPC Output signals
Name
OUT1
OUT2
Settings
TPSGAPC Non group settings (Basic)
Table 122: TPSGAPC Non group settings (Basic)
Parameter
Values (Range)
Pulse time
0...300
100
Type
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
s
1
Default
Description
0=False
Input 1
0=False
Input 2
Description
Output 1 status
Output 2 status
Default
0
1MRS758407 C
Pulse time
Description
Minimum pulse
time
SMU615
Technical Manual