Energizing Inputs (Sim0005); Binary Inputs - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Technical data
11.5

Energizing Inputs (SIM0005)

Table 294: Table 9: Energizing Inputs (SIM0005)
Description
Current sensor input
Voltage sensor input
11.6

Binary inputs

Table 295: Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
4
Equals the current range of 40....40000 A with 80A, 3mV/Hz Rogowski
5
Covers 6 kV...40.5 kV sensors with division ratio of 10 000:1. Secondary voltages 600mV/√3 ...
4,05V / √3. Range up to 2 x Rated
258
Rated current voltage (in sec-
ondary side)
Continuous voltage with-
stand
Input impedance at 50/60Hz
Rated voltage
Continuous voltage with-
stand
Input impedance at 50/60Hz
Adjust the binary input threshold voltage correctly. The threshold voltage
should be set to 70% of the nominal auxiliary voltage. The factory
default is 16 V to ensure the binary inputs' operation regardless of the
auxiliary voltage used (24, 48, 60, 110, 125, 220 or 250 V DC). However, the
default value is not optimal for the higher auxiliary voltages. The binary
input threshold voltage should be set as high as possible to prevent
any inadvertent activation of the binary inputs due to possible external
disturbances. At the same time, the threshold should be set so that
the correct operation is not jeopardized in case of undervoltage of the
auxiliary voltage.
Value
75 mV ... 9000 mV
125 V
2 MΩ
6 kV ... 40,5 kV
50 V
2 MΩ
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
16...176 V DC
<3 ms
1MRS758407 C
4
5
SMU615
Technical Manual