ABB RELION SMU615 Technical Manual page 210

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Measurement functions
VSMSQI Input signals
Table 239: VSMSQI Input signals
Name
U
0
U
1
U
2
7.1.9.4
Settings
VSMSQI Non group settings
Table 240: VSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Ps Seq V Hi high
0.00...4.00
Lim
Ps Seq V high limit
0.00...4.00
Ps Seq V low limit
0.00...4.00
Ps Seq V low low
0.00...4.00
Lim
Ps Seq V deadband 100...100000
Ng Seq V Hi high
0.00...4.00
Lim
Ng Seq V High limit 0.00...4.00
Ng Seq V low limit
0.00...4.00
Ng Seq V low low
0.00...4.00
Lim
Ng Seq V deadband 100...100000
Table continues on the next page
210
Type
SIGNAL
SIGNAL
SIGNAL
Unit
Step
xUn
1
xUn
1
xUn
1
xUn
1
1
xUn
1
xUn
1
xUn
1
xUn
1
1
Default
Description
0
Zero sequence volt-
age
0
Positive phase se-
quence voltage
0
Negative phase se-
quence voltage
Default
1=on
1.40
1.20
0.00
0.00
10000
0.20
0.05
0.00
0.00
10000
1MRS758407 C
Description
Operation Off / On
High alarm voltage
limit for positive
sequence voltage
High warning volt-
age limit for posi-
tive sequence volt-
age
Low warning volt-
age limit for posi-
tive sequence volt-
age
Low alarm voltage
limit for positive
sequence voltage
Deadband configu-
ration value for
positive sequence
voltage for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
High alarm voltage
limit for negative
sequence voltage
High warning volt-
age limit for nega-
tive sequence volt-
age
Low warning volt-
age limit for nega-
tive sequence volt-
age
Low alarm voltage
limit for negative
sequence voltage
Deadband configu-
ration value for
negative sequence
voltage for inte-
gral calculation.
SMU615
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents