ABB RELION SMU615 Technical Manual page 197

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
Parameter
Values (Range)
5=off
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
V high high limit
0.00...4.00
V high limit
0.00...4.00
V low limit
0.00...4.00
V low low limit
0.00...4.00
V deadband
100...100000
Table 217: VMMXU Non group settings (Advanced)
Parameter
Values (Range)
Measurement
1=RMS
mode
2=DFT
7.1.5.5
Monitored data
VMMXU Monitored data
Table 218: VMMXU Monitored data
Name
U12-kV
U23-kV
U31-kV
BLOCK
HIGH_ALARM
Table continues on the next page
SMU615
Technical Manual
Unit
Step
xUn
1
xUn
1
xUn
1
xUn
1
1
Unit
Step
Type
Values (Range)
FLOAT32
0.00...4.00
FLOAT32
0.00...4.00
FLOAT32
0.00...4.00
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
Measurement functions
Default
Description
1=1 out of 3
Number of phases
required by limit
supervision
1.40
High alarm voltage
limit
1.20
High warning volt-
age limit
0.00
Low warning volt-
age limit
0.00
Low alarm voltage
limit
10000
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Default
Description
2=DFT
Selects used meas-
urement mode
Unit
Description
xUn
Measured phase
to phase voltage
amplitude phase
AB
xUn
Measured phase
to phase voltage
amplitude phase
BC
xUn
Measured phase
to phase voltage
amplitude phase
CA
Block signal for
all binary out-
puts
High alarm
197