Sampled Measured Values Accuracy; Environmental Conditions - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Technical data
11.14

Sampled measured values accuracy

Table 304: Sampled measured values accuracy
Description
Phase current
Residual current
Phase voltage
Residual voltage (calculated)
11.15

Environmental conditions

Table 305: Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Atmospheric pressure
Table continues on the next page
1
In the 80 A/0.150 V at 50 Hz sensor applications the maximum range depends on the application
nominal:
....833 A (...31.237 mV/Hz) corresponds to 6000%I
833...1250 A (31.237...46.875 mV/Hz) corresponds to 4000%I
1250...2500 A (46.875...93.750 mV/Hz) corresponds to 2000%I
2500...4000 A (93.750...150.000 mV/Hz) corresponds to 1250%I
1
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 °C
2
For marging units with an LC communication interface the maximum operating temperature is
+70 °C
262
Value
1
20%...6000%I
n
Amplitude: 1% or ±0.003×I
Angle: ±2º
1%...5%I
n
Amplitude: 0.001×I
n
Angle: ±4º
5%...6000%I
n
Amplitude: ±1%
Angle: ±1º
80%...120% of U
n
Amplitude: ±0.5%
Angle: ±1º
1%...100% of U
n
Amplitude: ±0.5% or ±0.001×U
Angle: ±2º
Value
-25...+55°C (continuous)
-40...+85°C (<16 h)
<93%, non-condensing
86...106 kPa
n
n
n
n
1MRS758407 C
n
n
1 2
SMU615
Technical Manual