ABB RELION SMU615 Technical Manual page 201

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

1MRS758407 C
RESCMMXU Output signals
Table 222: RESCMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
7.1.6.4
Settings
RESCMMXU Non group settings
Table 223: RESCMMXU Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
A Hi high limit res
0.00...40.00
A high limit res
0.00...40.00
A deadband res
100...100000
Table 224: RESCMMXU Non group settings (Advanced)
Parameter
Values (Range)
Measurement
1=RMS
mode
2=DFT
7.1.6.5
Monitored data
RESCMMXU Monitored data
Table 225: RESCMMXU Monitored data
Name
Io-A
BLOCK
HIGH_ALARM
Table continues on the next page
SMU615
Technical Manual
Type
BOOLEAN
BOOLEAN
Unit
Step
xIn
1
xIn
1
1
Unit
Step
Type
Values (Range)
FLOAT32
0.00...40.00
BOOLEAN
0=False
1=True
BOOLEAN
0=False
1=True
Measurement functions
Description
High alarm
High warning
Default
Description
1=on
Operation Off / On
0.20
High alarm current
limit
0.05
High warning cur-
rent limit
2500
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Default
Description
2=DFT
Selects used meas-
urement mode
Unit
Description
xIn
Measured residu-
al current
Block signal for
all binary out-
puts
High alarm
201

Advertisement

Table of Contents
loading

Table of Contents