Basic functions
Fault indication
Fault
code
Internal Fault Card
73
error,X100
Internal Fault Card
74
error,X110
Internal Fault Card
75
error,X120
Internal Fault Card
76
error,X130
Internal Fault LHMI
79
module
Internal Fault RAM
80
error
Internal Fault ROM
81
error
Internal Fault EE-
82
PROM error
Internal Fault EE-
82
PROM error
Internal Fault FPGA
83
error
Internal Fault RTC
84
error
Internal Fault RTD
96
card error,X130
Table continues on the next page
42
Additional
Fast self-
information
recovery
attempt
(# of
attempts)
Card in slot X100
Yes (2)
is faulty.
Card in slot X110
Yes (2)
is faulty.
Card in slot X120
Yes (2)
is faulty.
Card in slot X130
Yes (2)
is faulty.
Runtime error:
Yes (2)
LHMI LCD error.
The fault indica-
tion may not be
seen on the LHMI
during the fault.
Runtime error: Er-
Yes (2)
ror in the RAM
memory on the
CPU module.
Runtime error: Er-
Yes (2)
ror in the ROM
memory on the
CPU module.
Start up error: Er-
No
ror in the EEPROM
memory on the
CPU module.
Start up error:
Yes (2)
CRC check failure
in the EEPROM
memory on boot-
up on the CPU
module.
Runtime error: Er-
Yes
ror in the FPGA on
the CPU module.
Start up error: Er-
Yes
ror in the RTC on
the CPU module.
Runtime error:
Yes
RTD card located
in slot X130 may
have permanent
fault. Temporary
Slow 10
Immediate
Action in permanent fault state
min self-
permanen
recovery (#
t IRF-
of
mode
attempts)
this. Detach the ethernet communi-
cation cable(s) from the communi-
cation module and reboot the relay.
If not recover,exchange the commu-
nication module in slot X000. "
Yes (3)
No
Exchange the hardware module in
slot X100.
Yes (3)
No
Exchange the hardware module in
slot X110.
Yes (3)
No
Exchange the hardware module in
slot X120.
Yes (3)
No
Check the plug-in unit connector
pins in the card by detaching the
plug-in unit. If pins are OK, ex-
change the hardware module in slot
X130.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restarting,
check LHMI connection cable and
connection to be proberly fixed. If
then not recovered by restarting,
exchange the LHMI module.
Yes (10)
No
If recovered by restarting, continue
relay normal operation. If not recov-
er by restarting, replace the relay,
most probably hardware failure in
CPU module.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
No
Yes
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restart-
ing, replace the relay, most probably
hardware failure in CPU module.
Yes (3)
No
Restart the relay. If recovered by re-
starting, continue relay normal op-
eration. If not recover by restarting,
exchange the hardware module in
slot X130.
1MRS758407 C
SMU615
Technical Manual