1MRS758407 C
Fault indication
Fault
code
Internal Fault Conf.
62
error,X000
Internal Fault Conf.
63
error,X100
Internal Fault Conf.
64
error,X110
Internal Fault Conf.
65
error,X120
Internal Fault Conf.
66
error,X130
Internal Fault Card
72
error,X000
Table continues on the next page
SMU615
Technical Manual
Additional
Fast self-
information
recovery
attempt
(# of
attempts)
Start up error:
No
Card in slot X000
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
Start up error:
No
Card in slot X100
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
Start up error:
No
Card in slot X110
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
Start up error:
No
Card in slot X120
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
Start up error:
No
Card in slot X130
is wrong type, is
missing, does not
belong to original
configuration or
card firmware is
faulty.
Card in slot X000
Yes (2)
is faulty.
Slow 10
Immediate
Action in permanent fault state
min self-
permanen
recovery (#
t IRF-
of
mode
attempts)
relay normal operation. If not recov-
er by restarting, exchange the com-
munication module including ARC
inputs in slot X000.
No
Yes
"Check that the communication
card in slot X000 is proper type and
properly installed. Check that the
plug-in unit is properly installed and
plug-in unit handle is properly fixed
to closed position. Then restart
the relay. If does not recover by re-
starting, it is hardware module fail-
ure most likely. Exchange the com-
munication module in slot X000.
In some rare cases also communi-
cation storm may cause this. De-
tach the ethernet communication
cable(s) from the communication
module and reboot the relay. If
not recover,exchange the communi-
cation module in slot X000. "
No
Yes
"Check that the card in slot X100
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X100."
No
Yes
"Check that the card in slot X110
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X110."
No
Yes
"Check that the card in slot X120
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X120."
No
Yes
"Check that the card in slot X130
is proper type and properly instal-
led. Check that the plug-in unit is
properly installed and plug-in unit
handle is properly fixed to closed
position. Then restart the relay. If
does not recover by restarting, it is
hardware module failure most likely.
Exchange the hardware module in
slot X130."
Yes (3)
No
"Check the plug-in unit connector
pins in the card by detaching the
plug-in unit. If pins are OK, ex-
change the communication module
in slot X000. In some rare cases al-
so communication storm may cause