Settings; Monitored Data - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Supervision functions
5.2.6.2
CCSPVC Output signals
Table 177: CCSPVC Output signals
Name
FAIL
ALARM
5.2.7

Settings

5.2.7.1
CCSPVC Non group settings
Table 178: CCSPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
0.05...0.20
Table 179: CCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Max operate cur-
1.00...5.00
rent
5.2.8

Monitored data

5.2.8.1
CCSPVC Monitored data
Table 180: CCSPVC Monitored data
Name
IDIFF
CCSPVC
152
Type
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
Unit
Step
xIn
0.01
Type
Values (Range)
FLOAT32
0.00...40.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS758407 C
Description
Fail output
Alarm output
Default
Description
1=on
Operation On / Off
0.05
Minimum operate
current differential
level
Default
Description
1.50
Block of the func-
tion at high phase
current
Unit
Description
xIn
Differential cur-
rent
Status
Technical Manual
SMU615

Advertisement

Table of Contents
loading

Table of Contents