Signals - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Condition monitoring functions
I
r
I
f
A
B
Calculation for estimating the remaining life
Figure 119
current of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if the
tripping current is 10 kA, one operation at 10 kA is equivalent to 30,000/60=500
operations at the rated current. It is also assumed that prior to this tripping,
the remaining life of the circuit breaker is 15,000 operations. Therefore, after one
operation of 10 kA, the remaining life of the circuit breaker is 15,000-500=14,500 at
the rated operating current.
Remaining life reduction =
Spring-charged indication
For normal operation of the circuit breaker, the circuit breaker spring should be
charged within a specified time. Therefore, detecting long spring-charging time
indicates that it is time for the circuit breaker maintenance. The last value of the
spring-charging time can be used as a service value.
Gas pressure supervision
The gas pressure supervision monitors the gas pressure inside the arc chamber.
When the pressure becomes too low compared to the required value, the circuit
breaker operations are locked. A binary input is available based on the pressure
levels in the function, and alarms are generated based on these inputs.
6.1.6

Signals

6.1.6.1
SSCBR Input signals
Table 196: SSCBR Input signals
Name
I_A
I_B
I_C
BLOCK
POSOPEN
Table continues on the next page
176
Rated operating current = 630 A
Rated fault current = 16 kA
Op number rated = 30000
Op number fault = 20
shows that there are 30,000 possible operations at the rated operating
Directional Coef
I
I
r
Type
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block input status
0=False
Signal for open po-
sition of apparatus
from I/O
1MRS758407 C
(Equation 8)
SMU615
Technical Manual