Settings; Monitored Data - ABB RELION SMU615 Technical Manual

Substation merging unit
Hide thumbs Also See for RELION SMU615:
Table of Contents

Advertisement

Protection related functions
4.1.6.2
TRPPTRC Output signals
Table 165: TRPPTRC Output signals
Name
TRIP
CL_LKOUT
4.1.7

Settings

4.1.7.1
TRPPTRC Non group settings (Basic)
Table 166: TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Trip pulse time
20...60000
Trip output mode
1=Non-latched
2=Latched
3=Lockout
4.1.8

Monitored data

4.1.8.1
TRPPTRC Monitored data
Table 167: TRPPTRC Monitored data
Name
TRPPTRC
132
Type
BOOLEAN
BOOLEAN
Unit
Step
ms
1
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS758407 C
Description
General trip output signal
Circuit breaker lockout out-
put (set until reset)
Default
Description
1=on
Operation Off / On
250
Minimum duration
of trip output sig-
nal
1=Non-latched
Select the opera-
tion mode for trip
output
Unit
Description
Status
Technical Manual
SMU615