4.12

Personnel safe restart lock -AS-

A frequently required application task is the protection of personnel against the restarting
of drives. This can be achieved by an electronic inhibit or with mechanical elements (posi-
tively driven relay contacts).
When positively driven relay contacts where used, either the net contactor in the mains
supply circuit switched off or the motor was disconnected from the servo amplifier by an
additional contactor.
The disadvantages of this method are :
— the DC bus link has to be charged up again at restart
— wear on the contacts of the contactors, caused by switching under load
— extensive wiring required, with additional switching components
The restart lock -AS- avoids these disadvantages.
The conceptual examination of the function "safe stop" (called restart lock AS in the follo-
wing) was accomplished by the BG-Institute for Occupational Safety and Health and the
classification in category 3 according to EN 954-1 was confirmed.
Advantages of the restart lock -AS- :
— the DC bus link remains charged up, since the mains supply line remains active
— only low voltages are switched, so there is no contact wear
— very little wiring is required
— the functionality and the personnel safety when using the circuit recommendations in
4.12.1

Technical data and pinning

Input voltage
Input current
Peak current
4.12.2

Environment

Since the servo amplifier meets enclosure IP20, you must select the environment ensu-
ring a safe operation of the servo amplifier. The environment must meet enclosure IP54
at least.
4.12.3

Wiring

If the wiring leads outside the demanded enclosure (IP54), the cables must be laid dura-
bly (firmly), protected from outside damage (e.g. laying in a cable duct), in different sheat-
hed cables or protected individually by grounding connection.
If wiring remains within the demanded enclosure, then it has to meet the requirements of
the standard EN 60204-1, section 14-3.
®
SERVOSTAR
300 Installation Manual
this documentation have been approved by the Trade Liability Association.
20V..30V
40mA – 75mA (Ieff)
220mA (Is)
12/05