Emergency Stop Strategies - Danaher Motion Kollmorgen SERVOSTAR 300 Series Assembly, Installation, Setup

Digital servo amplifier
Table of Contents

Advertisement

Technical description
2.14.2

Emergency Stop strategies

The Emergency Stop function is defined in EN 60204 (VDE 0113), Para. 9.2.5.4.
Implementation of the Emergency Stop function :
Wiring recommendation can be found in the Application Note "Stop and Emergency Stop
Functions".
Category 0:
Category 1:
26
The controller enable is switched to "disable", the electrical supply is disconnected.
The drive must be held by an electromechanical holding device (brake).
In multi-axis systems with a coupled DC bus link, the motor cable must also be
disconnected by a changeover switch (a contactor, such as the Siemens
3RT1516-1BB40) and short-circuited by resistors connected in a star configuration.
If hazardous conditions can result from an Emergency Stop switch-off with an
uncontrolled run-down, the drive can be switched off after a controlled shutdown.
Stop Category 1 permits electromotoric (i.e. regenerative) braking with a switch-off
when zero speed has been reached. Safe shutdown can be achieved if the loss of
the electrical supply is not evaluated as a fault and the control system takes over
the disabling of the servo amplifier.
In normal circumstances, only the supply power is switched off in a safe manner.
The 24V auxiliary supply remains switched on.
12/05
SERVOSTAR
Kollmorgen
®
300 Installation Manual