UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Figure 3-16 Securing the antiseismic kits to the cabinet
Step 3 Reinstall the rear panel.
Step 4 Adjust the cabinet position so that the expansion bolt holes are aligned with the
eight holes at the bottom of the cabinet.
Step 5 Secure the two antiseismic kits at the front and rear of the cabinet to the floor
using eight M12 expansion bolts, as shown in
Figure 3-17 Securing the antiseismic kits to the floor
----End

3.2.3.2 Connecting an Ambient T/H Sensor

Procedure
Step 1 Connect the RJ11 port on the ambient T/H sensor to the COM1 port on the
monitoring interface card.
Issue 02 (2020-11-10)
Copyright © Huawei Technologies Co., Ltd.
Figure
3-17.
3 Installation