Motor
2. heat
3. noise
1. power input
voltage
2. inverter
Operation
output voltage
status
3. inverter
parameters
output current
4. internal
temperature
8.2 Periodic Maintenance
Customer should I5000ck the drive every 3 months or 6 months according to the actual
environment
8.2.1 I5000ck whether the screws of control terminals are loose. If so, tighten them with a
screwdriver;
8.2.2 I5000ck whether the main circuit terminals are properly connected; whether the mains
cables are over heated;
8.2.3 I5000ck whether the power cables and control cables are damaged, I5000ck
especially for any wear on the cable tube;
8.2.4 I5000ck whether the insulating tapes around the cable lugs are stripped;
8.2.5 Clean the dust on PCBs and air ducts with a vacuum cleaner;
8.2.6 For drives that have been stored for a long time, it must be powered on every 2 years.
When supplying AC power to the drive, use a voltage regulator to raise the input voltage to rated
input voltage gradually. The drive should be powered for 5 hours without load.
8.2.7 Before performing insulation tests, all main circuit input/output terminals should be short-
circuited with conductors. Then proceed insulation test to the ground. Insulation test of single
main circuit terminal to ground is forbidden; otherwise the drive might be damaged. Please use a
500V Mega-Ohm-Meter.
2. point
thermometer
3. listening
1. voltmeter
2. rectifying
voltmeter
3. ammeter
4. point
thermometer
89
2. No abnormal heat.
3. No abnormal noise.
1. satisfying the specification
2. satisfying the specification
3. satisfying the specification
4. temperature rise is lower
than 40℃