PB.06 is a percentage of the inverter's rated current.
PB.07 defines the decrease rate of output frequency when this function is active. If PB.06 is
too small, overload fault may occur. If it is too big, the frequency will change too sharply and
therefore, the feedback energy of motor will be too large and may cause over-voltage fault.
This function is always enabled during acceleration or deceleration.
Notice:
During auto current limiting process, the inverter's output frequency may
change; therefore, it is recommended not to enable the function when
requires the inverter's output frequency stable.
During auto current limiting process, if PB.06 is too low, the overload
capacity will be impacted.
Please refer to following figure.
6.13 PC Group--Serial Communication
Function
Code
PC.00
This parameter determines the slave address used for communication with master. The value
"0" is the broadcast address.
Function
Code
Figure 6.29 Current limiting protection function.
Name
Local address
Name
Description
1~247
Description
76
Setting
Factory
Range
Setting
0~247
1
Setting
Factory
Range
Setting