IACDRIVE I5000 Series Operation Manual page 42

Sensorless vector control inverter
Table of Contents

Advertisement

e.
During the auto-tuning, press the STOP/RST will stop the auto-tuning.
Notice: Only keypad can control the auto-tuning. P0.12 will restore to 0 automatically
when the auto-tuning is finished or cancelled.
2: Static auto-tuning:
If it is difficult to dis conne ct the loa d, s ta tic a uto -tuning is recommended.
The ope ra tion proce s s is the s a m e a s rota tion a uto -tuning except step c.
Notice: The Mutual inductance and current without load will not be detected by static auto-
tuning, if needed user should input suitable value according to experience.
Function
Code
P0.13
parameters
0: No action
1: Inverter restores all parameters to factory setting except P2 group.
2: Inverter clear all fault records.
This function code will restore to 0 automatically when complete the function operation.
Function
Code
P0.14
AVR function
AVR ( Auto Voltage Regulation) function ensure the output voltage of inverter stable no matter
how the DC bus voltage changes. During deceleration, if AVR function is disabled, the
deceleration time will be short but the current will be big. If AVR function is enabled all the time,
the deceleration time will be long but the current will be small.
6.2 P1 Group--Start and Stop Control
Function
Name
Code
Start
P1.00
Mode
Name
0: No action
Restore
1: Restore factory setting
2: Clear fault records
Name
0:Disabled
1:Enabled all the time
2: Disabled during
deceleration
0: Start directly
1: DC braking and start
Description
Description
Description
40
Setting
Factory
Range
Setting
0~2
0
Setting
Factory
Range
Setting
0~2
1
Setting
Factory
Range
Setting
0~1
0