● The person without passing the training manipulate the device or any rule in the
"Warning" being violated, will cause severe injury or property loss. Only the
person, who has passed the training on the design, installation, commissioning
and operation of the device and gotten the certification, is permitted to operate
this equipment.
● Input power cable must be connected tightly, and the equipment must be
grounded securely.
● Even if the inverter is not running, the following terminals still have dangerous
voltage:
- Power Terminals: R, S, T
- Motor Connection Terminals: U, V, W.
●When power off, should not install the inverter until 5 minutes after, which can
ensure the device discharge completely.
● The section area of grounding conductor must be no less than that of power
supply cable.
●When moving the inverter please lift by its base and don't lift by the panel.
Otherwise may cause the main unit fall off which may result in personal injury.
● Install the inverter on the fireproofing material (such as metal) to prevent fire.
● When need install two or more inverters in one cabinet, cooling fan should be
provided to make sure that the air temperature is lower than 45°C. Otherwise it
could cause fire or damage the device.
3.1 Environmental Requirement

3.INSTALLATION

WARNING
CAUTION
9