P8.04
The meaning and factory setting of P8.03 and P8.04 is the same as P0.08 and P0.09. No
matter what the value of P1.00 and P1.05 are, jog will start as start directly mode and stop
as deceleration to stop mode.
Function
Code
P8.05
P8.06
By means of setting skip frequency, the inverter can keep away from the mechanical
resonance with the load. P8.05 is centre value of frequency to be skipped.
Notice:
If P8.06 is 0, the skip function is invalid.
If P8.05 is 0, the skip function is invalid no matter what P8.06 is.
Operation is prohibited within the skip frequency bandwidth, but changes
during acceleration and deceleration are smooth without skip.
The relation between output frequency and reference frequency is shown in following figure.
Function
Code
P8.07
P8.08
Jitter frequency
Jog deceleration time
Name
Skip frequency
Skip frequency
bandwidth
Figure 6.16 Skip frequency diagram.
Name
Traverse
amplitude
0.1~3600.0s
Description
0.00~P0.04
0.00~P0.04
Description
0.0~100.0%
0.0~50.0%
63
0.1~3600.0
Factory
Setting Range
0.00~P0.04
0.00~P0.04
Setting
Factory
Range
Setting
0.0~100.0
0.0%
0.0~50.0
0.0%
Depend
on model
Setting
0.00Hz
0.00Hz