IACDRIVE I5000 Series Operation Manual page 80

Sensorless vector control inverter
Table of Contents

Advertisement

Communication
PC.03
This parameter can be used to set the response delay in communication in
order to adapt to the MODBUS master. In RTU mode, the actual communication delay should
be no less than 3.5 characters' interval; in ASCII mode, 1ms.
Function
Code
Communication
PC.04
When the value is zero, this function will be disabled. When communication interruption is longer
than the non-zero value of PC.04, the inverter will alarm communication error (CE).
Function
Code
Communication
PC.05
error action
0: When communication error occurs, inverter will alarm (CE) and coast to stop.
1: When communication error occurs, inverter will omit the error and continue to run.
2: When communication error occurs, if P0.01=2, inverter will not alarm but stop according to
stop mode determined by P1.05. Otherwise it will omit the error.
3: When communication error occurs, inverter will not alarm but stop according to stop
mode determined by P1.05.
Function code
PC.06
delay time
Name
timeout delay
Name
0: Alarm and coast to
stop
1: No alarm and
continue to run
2: No alarm but stop
according to P1.05 (if
P0.01=2)
3: No alarm but stop
according to P1.05
Transmission response
0~200ms
Description
0.0: Disabled
0.1~100.0s
Description
Name
78
0~200
5ms
Setting
Factory
Range
Setting
0~100.0
0.0s
Setting
Factory
Range
Setting
0~3
1
Setting range
0000~1111【0000】