IACDRIVE I5000 Series Operation Manual page 118

Sensorless vector control inverter
Table of Contents

Advertisement

02
If the operation fails, the inverter will reply a message formed by failure command and error
code. The failure command is (Command+0x80). The error code indicates the reason of
the error; see the table below.
Value
Name
Illegal
01H
command
Illegal data
02H
address.
03H
Illegal value
06H
Slave busy
Password
10H
error
11H
I5000ck error
Written not
12H
allowed.
System
13H
locked
Protocol data unit format of writing single parameter:
I5000
The command from master can not be executed. The reason
maybe:
1. This command is only for new version and this version
can not realize.
2.
Slave is in fault status and can not execute it.
Some of the operation addresses are invalid or not allowed
to access.
When there are invalid data in the message framed received
by slave.
Note: This error code does not indicate the data value to
write exceed the range, but indicate the message frame is a
illegal frame.
Inverter is busy(EEPROM is storing)
The password written to the password I5000ck address is not
same as the password set by P7.00.
The CRC (RTU mode) or LRC (ASCII mode) I5000ck not
passed.
It only happen in write command, the reason maybe:
1.
the data to write exceed the range of according
parameter
2.
The parameter should not be modified now.
3.
The terminal has already been used.
When password protection take effect and user does not
unlock it, write/read the function parameter will return this
error.