Specifications Of Breaker, Cable, Contactor And Reactor - IACDRIVE I5000 Series Operation Manual

Sensorless vector control inverter
Table of Contents

Advertisement

4.4 Specifications of Breaker, Cable, Contactor and Reactor

4.4.1 Specifications of breaker, cable and contactor
Model No.
I500D423A
I50D7523A
I501D523A
I502D223A
I50D75G01D5P43A
I501D5G02D2P43A
I502D2G03D7P43A
I504D0G05D5P43A
I505D5G07D5P43A
I507D5G0011P43A
I50011G0015P43A
I50015G0018P43A
I518D5G0022P43A
I50022G0030P43A
I50030G0037P43A
I50037G0045P43A
I50045G0055P43A
I50055G0075P43A
I50075G0090P43A
I50090G0110P43A
I50110G0132P43A
I50132G0160P43A
I50160G0185P43A
I50185G0200P43A
I50200G0220P43A
I50220G0250P43A
I50250G0280P43A
I50280G0315P43A
I50315G0350P43A
I5000000350G43A
Input / Output
Circuit
Cable(mm
Breaker (A)
16
16
20
32
16
16
16
25
25
40
63
63
100
100
125
160
200
200
250
315
400
400
630
630
630
800
800
1000
1200
1280
16
AC Contactor
2
)
1.5
2.5
4
6
2.5
2.5
2.5
4
4
6
6
6
10
16
25
25
35
35
70
70
95
150
185
185
240
150x2
150x2
185x2
240x2
240x2
(A)
10
10
16
20
10
10
10
16
16
25
32
50
63
80
95
120
135
170
230
280
315
380
450
500
580
630
700
780
900
960

Advertisement

Table of Contents
loading

Table of Contents