P5.12
P5.13
These parameters determine the relationship between analog input voltage and the
corresponding setting value. When the analog input voltage exceeds the range between lower
limit and upper limit, it will be regarded as the upper limit or lower limit.
The analog input FV can only provide voltage input, and the range is 0V~10V.
For different applications, the corresponding value of 100.0% analog setting is different. For
details, please refer to description of each application.
Notice: FV lower limit must be less or equal to FV upper limit.
Figure 6.14 Relationship between AI and corresponding setting.
FV filter time constant is effective when there are sudden changes or noise in the analog input
signal. Responsiveness decreases as the setting increases.
Function Code
P5.14
P5.15
P5.16
P5.17
FV upper limit
Corresponding setting
FV filter time constant
Name
FI lower limit
FI lower limit
corresponding setting
FI upper limit
FI upper limit
corresponding setting
53
-100.0~100.0
[100.0%]
0.00~10.00[0.10s]
Setting Range
0.00~10.00[0.00V]
-100.0~100.0
[0.0%]
0.00~10.00[5.00V]
-100.0~100.0
[100.0%]