Advertisement

37kW and above: 40.0s
Function
Name
Code
Running
P0.10
direction
selection
Notice:
The rotation direction of motor is corresponding to the wiring of motor.
When the factory setting is restored (P0.13 is set to be 1), the rotation direction of
motor may be changed. Please be cautious to use.
Function
Code
P0.11
Carrier frequency
The following table is the relationship between power rating and carrier frequency.
Carrier f
Model
G Model: 0.4kW~11kW
P Model: 0.75kW~15kW
G Model: 15kW~55kW
P Model: 18.5kW~75kW
G Model: 75kW~300kW
P Model: 90kW~315kW
Description
0: Forward
1: Reverse
2: Forbid reverse
Name
0.5~15.0kHz
Figure 6.2 Effect of carrier frequency.
Highest Carrier f
( kHz )
15
8
6
Setting
Description
Range
0.5~15.0
Lowest Carrier f
( kHz )
38
Setting
Factory
Range
Setting
0~2
0
Factory
Setting
Depend on
model
Factory setting
( kHz )
1
1
1
8
4
2