Under the third-class menu, if the parameter has no flickering bit, it means the function code
cannot be modified. The possible reasons could be:
This function code is not modifiable parameter, such as actual detected parameter,
operation records and so on;
This function code is not modifiable in running status, but modifiable in stop status
5.2.2 Fault reset
If the inverter has fault, it will prompt the related fault information. User can use STOP/RST or
according terminals determined by P5 Group to reset the fault. After fault reset, the inverter is at
stand-by state. If user does not reset the inverter when it is at fault state, the inverter will be at
operation protection state, and can not run.
5.2.3 Motor parameter auto-tuning
Figure 5.2 Flow chart of parameter setting.
29