If P1.11 is set to be 1, when power on and FWD/REV terminal is active, inverter will start
automatically.
This function may cause the inverter restart automatically, please be cautious.
6.3 P2 Group--Motor Parameters
Function
Code
P2.00
0: Applicable to constant torque load
1: Applicable to variable torque load (i.e. fans, pumps)
I5000 series inverters provide the G/P integration function. The adaptive motor power used for
constant torque load (G model) should be one grade less than that used for variable torque load
(P model).
To change from G model to P model, procedures are as follow:
Set P2.00 to be 1;
Input motor parameters in P2 group again..
Function
Code
P2.01
P2.02
P2.03
P2.04
P2.05
Notice:
In order to achieve superior performance, please set these parameters according to
motor nameplate, then perform auto-tuning.
The power rating of inverter should match the motor. If the bias is too big, the
control performances of inverter will be deteriorated distinctly.
Reset P2.01 can initialize P2.02~P2.10 automatically.
Name
G/P option
Name
Motor rated
power
Motor rated
0.01Hz~P0.04
frequency
Motor rated
speed
Motor rated
voltage
Motor rated
current
Description
0: G model
1: P model
Description
Setting Range
0.4~900.0kW
0~36000rpm
0~2000V
0.8~2000.0A
44
Setting
Range
0~1
Factory
Setting
Depend on
0.4~900.0
0.01~P0.04
50.00Hz
Depend on
0~36000
Depend on
0~2000V
Depend on
0.8~2000.0
Factory
Setting
0
model
model
model
model