When P0.03 is set to be 0, this parameter is the initial value of inverter reference frequency
Function
Code
P0.08
Acceleration time 0
P0.09
Deceleration time 0
Acceleration time is the time of accelerating from 0Hz to maximum frequency (P0.04).
Deceleration time is the time of decelerating from maximum frequency (P0.04) to 0Hz. Please
refer to following figure.
When the reference frequency is equal to the maximum frequency, the actual acceleration and
deceleration time will be equal to the P0.08 and P0.09 respectively. When the reference
frequency is less than the maximum frequency, the actual acceleration and deceleration time
will be less than the P0.08 and P0.09 respectively. The actual acceleration (deceleration) time =
P0.08 (P0.09) * reference frequency/P0.04. I5000 series inverter has 2 groups of acceleration
and deceleration time.
1st group: P0.07, P0.08 2nd
group: P8.00, P8.01
The acceleration and deceleration time can be selected by combination of multifunctional ON-
OFF input terminals determined by P5 Group. The factory setting of acceleration and
deceleration time is as follow:
5.5kW and below: 10.0s
7.5kW~30kW: 20.0s
Name
Figure 6.1 Acceleration and deceleration time.
Description
Setting Range
0.0~3600.0s
0.0~3600.0
0.0~3600.0s
0.0~3600.0
37
Factory
Setting
Depend on
model
Depend on
model