IACDRIVE I5000 Series Operation Manual page 115

Sensorless vector control inverter
Table of Contents

Advertisement

Different respond delay can be set through drive's parameters to adapt to different needs. For
RTU mode, the respond delay should be no less than 3.5 bytes interval, and for ASCII mode,
no less than 1ms.
The main function of Modbus is to read and write parameters. The Modbus protocol
supports the following commands:
0x03
Read inverter's function parameter and status parameters
0x06
Write single function parameter or command parameter to inverter
All drive's function parameters, control and status parameters are mapped to Modbus R/W
data address.
The data addresses of each function parameters please refer the sixth column of chapter 9.
The data address of control and status parameters please refer to the following table.
Parameter
Description
Control
command
Inverter status
Communication
setting
Address
0001H: Forward
0002H: Reverse
0003H: JOG forward
0004H: JOG reverse
1000H
0005H: Stop
0006H: Coast to stop
0007H: Reset fault
0008H: JOG stop
0001H: Forward running
0002H: Reverse running
1001H
0003H: Standby
0004H: Fault
Communication Setting Range
(-10000~10000)
Note: the communication setting is the
percentage of the relative value
(-100.00%~100.00%). If it is set as
2000H
frequency source, the value is the
percentage of the maximum frequency
(P0.04). If it is set as PID (preset value
Meaning of value
113
R/W
Feature
W/R
R
W/R