8 Grid Dispatching Function
Subsequent Operation
Delete digital input manner: select a digital input manner that needs to be deleted, and click
Clear data.
8.3.1.6 DRM mode
When using the digital signal at the DI port (DI1 ~ DI4) of the Logger1000 as the dispatching
input, set the active control mode to DRM mode.
step 1 Click Power control→Active power to enter the active power interface.
step 2 Set the active control mode to DRM mode and click Save.
- - End
8.3.1.7 Country mode
If the dispatching input must be the national power dispatching instruction, the Rctive
Control Mode is set to Country mode.
step 1 Click Power control→Active power to enter the active power interface.
step 2 Set the active control mode to Country mode.
step 3 Select a country and PPC type, and click Save.
- - End
8.3.1.8 Scheduling Prohibited
Set the active control mode to Scheduling prohibited if the Logger1000 is prohibited to
perform active dispatching on the inverter.
step 1 Click Power control→Active power to enter the active power interface.
step 2 Set the active control mode to Scheduling prohibited and click Save.
- - End
8.3.2 Reactive Power
8.3.2.1 Disable
If the grid company does not need the power plant to adjust the voltage at the grid-
connection point, and the inverter does not need to cooperate with the grid for reactive
power compensation, the inverter keeps operating in the reactive-forbidden output state,
and the Reactive Control Mode is set to Disable.
step 1 Click Power control→Reactive power to enter the reactive power interface.
step 2 Set the Reactive Control Mode to Disable and click Save.
- - End