8 Grid Dispatching Function
8.3.2.6 Country Mode
If the dispatching input must be the national power dispatching instruction, the Reactive
Control Mode is set to Country mode.
step 1 Click Power control→Reactive power to enter the reactive power interface.
step 2 Set the Reactive Control Mode to Country mode.
step 3 Select a country, PPC type, and instruction type, and click Save.
- - End
8.3.2.7 Scheduling prohibited
Set the Reactive Control Mode to Scheduling prohibited if the Logger1000 is prohibited
to perform reactive dispatching on the inverter.
step 1 Click Power control→Reactive power to enter the reactive power interface.
step 2 Set the Reactive Control Mode to Scheduling prohibited and click Save.
- - End
8.3.3 Emergency Button
In inverters need to be stopped in batch, select the button Emergency Button.
Click Power control→Emergency button to enter the corresponding interface.
Parameter
Emergency button
DI port
76
Description
Enable: The emergency button is turned on, and inverters are
stopped in batch.
Note:When the emergency button is recovered, and inverters are
still in standby mode.It is required to boot the inverters manually
via logger or other approaches.
Associated with DI5 channel
User Manual