Parameters
Parameter Type
Time Calibration
When the country is set to China, the value for Scheduling Mode is set to DC Energy Storage
by default.
step 4 Click Save.
- - End

8.2.1.7 Disable Dispatching

Set Active Control Mode to Disable Dispatching to prohibit the Data Logger from
performing reactive dispatching on the inverter.
step 1 Click Power Control > Active Power to enter the Active Power page.
step 2 Set Active Control Mode to Disable Dispatching, and click Save.
- - End

8.2.2 Reactive Power

8.2.2.1 Disable Output

If the grid company does not need the power plant to adjust the voltage at the grid-
connection point, and the inverter does not need to cooperate with the grid for reactive
power compensation, the inverter keeps operating in the reactive-forbidden output state, and
the Reactive Control Mode is set to Disable Output.
step 1 Click Power Control > Reactive Power to enter the Reactive Power page.
step 2 Set Reactive Control Mode to Disable Output, and click Save.
- - End
Description
• When selecting Plant Parameter, set Plant Information and
PV Module Capacity further.
• When selecting Device Parameter, click Detailed Device
Parameter to view and set device information.
Calibrate the time as needed. Calibration range: -10~10. When
the system time of Data Logger < the time adjusted after Time
Calibration, or the time of Data Logger < the NTP synchronized
time, Time Validity will be displayed as Invalid, at which time
Data Logger will send a stop command to the inverter, until Time
Calibration or NTP synchronization operation is performed.
8 Grid Dispatching Function