Page 1
M M a a n n u u a a l l L L o o g g g g e e r r 3 3 0 0 0 0 0 0 - - U U E E N N - - V V e e r r 1 1 7 7 - - 2 2 0 0 1 1 9 9 0 0 4 4 Logger3000-UEN-Ver17-201904 Logger3000...
4 Installation Flow ..................11 5 Unpacking and Storage ................13 5.1 Scope of Delivery ..................13 5.2 Identifying the Logger3000 ................ 14 5.3 Checking upon Receiving ................14 5.4 Storage ...................... 15 6 Mechanical Installation ................16 6.1 Location Selection..................16 6.2 Installation Tools..................
Page 4
7.4.2 Connecting to the Device with RJ45 Port........... 25 7.4.3 Connecting to the Meteo Station ............26 7.4.4 Connecting to the Energy Meter............27 7.5 Ethernet Port....................28 7.6 PLC Port..................... 29 7.7 Connecting to the AC Power Supply ............30 7.8 Connecting to the DC Power Supply ............
Page 5
9.9.8 Cloud Service Setting................ 47 9.9.9 Country and Region Setting .............. 49 9.9.10 About ..................... 49 9.10 Maintenance .................... 49 10 Grid Dispatching ..................51 10.1 Function Description ................51 10.2 Grid Dispatching Plans ................51 10.3 EMU Setting..................... 52 10.4 Local Power Regulation................
1.2 Target Group This manual is applicable to technical personnel who are responsible for the installation, operation and maintenance of the Logger3000 and to users who need to perform daily operation. Readers should have the following qualifications: Have some knowledge of electrical and electric cabling and mechanical knowledge;...
Page 8
S S y y m m b b o o l l s s E E x x p p l l a a n n a a t t i i o o n n Disconnect the Logger3000 from all the external power sources before service! Hot surface! Do not touch! Risk of electric shock! If not avoided, lethal hazard can be caused.
Any reproduction or disclosure, even partially, of the contents of this manual is strictly prohibited without prior written authorization of SUNGROW. The content of the manual will be periodically updated or revised as per the product development. It is probably that there are changes in manuals for the subsequent module edition.
Incorrect operation or misuse of the device may cause: damage to personnel safety of the operators or the third party • damage to the Logger3000 or other properties belong to the operators or the third • party Therefore, the following safety instructions must be read and always kept in mind prior to any work.
Page 11
M M a a i i n n t t e e n n a a n n c c e e a a n n d d R R e e p p l l a a c c e e m m e e n n t t The maintenance of the Logger3000 can only be performed by qualified personnel from SUNGROW or other qualified personnel.
S S u u p p p p o o r r t t o o f f D D e e v v i i c c e e C C o o n n n n e e c c t t i i o o n n The Logger3000 can be connected to devices in the PV system via an RS485 bus, and it can be also connected to SUNGROW string inverter equipped with the PLC communication function through the PLC cable.
3.2 Application scenario The Logger3000 is connected to the inverter, transformer, Meteo Station, and energy meter in the PV system via RS485 bus, or it can be connected to SUNGROW string inverter equipped with PLC communication function through PLC (power line carrier communication) bus.
Page 14
3 Product Introduction User Manual f f i i g g u u r r e e 3 3 - - 2 2 Star networking...
C C o o n n n n e e c c t t i i o o n n t t h h r r o o u u g g h h R R o o u u t t e e r r As shown in the figure below, the Logger3000 can be directly connected to the iSolarCloud through a router.
3 Product Introduction User Manual I I n n d d i i c c a a t t o o r r D D e e s s c c r r i i p p t t i i o o n n I I n n d d i i c c a a - - N N a a m m e e t t o o r r...
Installation Flow The following figure shows the overall installation flow of Logger3000. R R e e f f e e r r e e n n c c e e c c h h a a p p t t e e r r N N o o .
Page 18
4 Installation Flow User Manual R R e e f f e e r r e e n n c c e e c c h h a a p p t t e e r r N N o o . . P P r r o o c c e e d d u u r r e e Check before commissioning "8.1 Inspection before Commissioning"...
Logger3000 5.2 Identifying the Logger3000 The type and key technical parameters of the Logger3000 can be found on the nameplate. The nameplate is attached to the upper right corner of the Logger3000, shown by A in the figure below.
If the Logger3000 is not to be installed immediately after receiving, observe the following requirements to store it properly: The Logger3000 should be store in its original packing case and placed in a well- • ventilated, dry, and tidy room.
I I n n s s t t a a l l l l a a t t i i o o n n L L o o c c a a t t i i o o n n R R e e q q u u i i r r e e m m e e n n t t s s With the ingress of protection IP 20, the Logger3000 can be installed only indoors.
User Manual 6 Mechanical Installation 6.3 Installing Logger3000 The Logger3000 can be installed anywhere in the room meeting the installation environment requirements. Wall-mounted installation and rack-mounted installation are supported. 6.3.1 Wall-Mounted Installation Avoid drilling holes in the utility pipes and/or cables attached to back of the wall! Turn on the vacuum cleaner and wear safety goggles and dust mask throughout the drilling process to avoid dust inhalation or contact with eyes.
Page 24
I I n n s s t t a a l l l l M M o o u u n n t t i i n n g g E E a a r r s s a a n n d d B B o o t t t t o o m m S S u u p p p p o o r r t t e e r r s s Anchor the mounting ears and bottom supporters to the Logger3000 with supplied M4x8 cross recessed countersunk head screws.
The fastening torque is 1.8-2.4N·m, and the anchoring method is as follows: step 1 Mark positions on the rack according to dimensions of the Logger3000. step 2 Drill holes on the rack with a hammer drill of φ6mm.
Page 26
User Manual step 3 Level the mounting ears with the drilled holes on the rack. step 4 Fix the Logger3000 in the sequence of screws, mounting ears, rack, and nuts. - - - - E E n n d d...
Incorrect wiring will cause device damage or even personal injury. All cables must be intact, well insulated, appropriately dimensioned, and firmly connected. 7.2 Port Introduction External wiring terminals are located at the bottom of Logger3000, and the wiring area is shown in the figure below.
Page 28
Dry contact input interface USB port USB-HOST Reserved SD port Reserved Used for debugging of the Debug Debug port Logger3000 Used for hardware reset of Reset Logger3000 Relay output interface Digital output DO1~DO4 Relay specification: 250Vac/1A or 30Vdc/1A PT1, PT2, AI1~AI4...
• Logger3000 with the help of communication devices. Ensure that the Logger3000 has been powered down before installing or removing the GPS antenna. R R S S 4 4 8 8 5 5 c c o o m m m m u u n n i i c c a a t t i i o o n n p p o o r r t t s s For the RS485 communication ports (A1B1~A6B6), the communication distance should be no more than 1,000m.
Page 30
C C o o n n n n e e c c t t i i n n g g t t o o M M u u l l t t i i p p l l e e I I n n v v e e r r t t e e r r s s Multiple inverters are connected to the Logger3000 in the RS485 daisy chain manner. If more than 15 inverters are connected on the RS485 bus, it is recommended to connect a 120Ω...
RS485 port of the Logger3000. step 4 Connect the wiring terminal to the terminal "A1B1~A6B6" of the Logger3000. - - - - E E n n d d 7.4.2 Connecting to the Device with RJ45 Port...
2 Strip the protection layer and insulation layer of the communication cable with a wire striper, as shown in the figure below. step 3 Connect the stripped cable to the RS485 port of the Logger3000, as shown in the figure below.
7 Electrical Connection User Manual step 3 Connect the stripped cable to the RS485 port of the Logger3000, as shown in the figure below. - - - - E E n n d d 7.5 Ethernet Port The Logger3000 is equipped with two Ethernet ports: ETH1 and ETH2. The function of the ETH1 is reserved.
User Manual 7 Electrical Connection 7.6 PLC Port Integrated with PLC master node, the Logger3000 can be connected to the inverter integrated with PLC slave node and achieve PLC communication by using existing power cable. P P r r e e p p a a r r a a t t i i o o n n b b e e f f o o r r e e w w i i r r i i n n g g Disconnect the transformer from the grid.
• connected. 7.7 Connecting to the AC Power Supply The Logger3000 can be connected to a power source with voltage ranging from 110 to 277Vac. step 1 Lead the external power supply cable to the wiring area of the Logger3000.
2 Strip the power supply cable by an appropriate length and crimp it to an euro style terminal. step 3 Insert the euro style terminal to the external jack "24V (+、-)" of the Logger3000. - - - - E E n n d d...
2 Crimp the stripped cable into an appropriate euro style terminal. step 3 Secure the grounding cable to the grounding hole of the Logger3000, as shown in the figure below. D D e e s s c c r r i i p p t t i i o o n n N N o o .
Configure the address of iSolarCloud if running data needs to be uploaded to iSolarCloud. If the Logger3000 is used in mainland China, it is unnecessary to configure the address. If the Logger3000 is used in regions other than mainland China, set the address to api.isolarcloud.com.hk and the port to 19999.
1366 x 768 CPU frequency higher than 2.5GHz 9.2 Preparation before Login Connect the PC to the ETH2 port of the Logger3000, and the IP address of the ETH • port is 192.168.1.100 by default. Set the PC IP address to a value within the same network segment as that of the IP •...
User Manual 9 Web Interface - - - - E E n n d d 9.4 Web Interface The WEB interface is as follows: D D e e s s c c r r i i p p t t i i o o n n N N o o .
Note: * is optional. 9.6 Operation Flow Operate as follows to log into the Logger3000 for the first time. S S t t e e p p R R e e f f e e r r e e n n c c e e c c h h a a p p t t e e r r 1.
View information such as the real-time data of devices (for example, inverter) • connected to the Logger3000. Set parameters of devices managed by the Logger3000, including initial parameters, • running parameters, protection parameters, and system parameters. The left sidebar "Overview" displays a list of devices currently managed by the Logger3000.
2 Select a device name. step 3 Click "Search". - - - - E E n n d d 9.8 Device Management The "Management" menu is used to manage devices connected to the Logger3000 and configure addresses for them.
User Manual 9 Web Interface 9.8.1 Searching Device The function is used to search for devices equipped with searching function, such as string inverter, and allocate address to them. Devices can be searched for in the following two manners: Searching by Port •...
Page 46
9 Web Interface User Manual 9.8.1.3 View Searched Devices View the searched devices in the following three manners on the "Search device" interface. D D e e v v i i c c e e F F u u n n c c t t i i o o n n b b u u t t t t o o n n Display devices All devices searched Devices searched by port...
9.8.2 Device Operation This function is used to add, modify, and delete devices connected to the Logger3000. A A d d d d D D e e v v i i c c e e Click "Add device"...
Page 48
E E d d i i t t i i n n g g D D e e v v i i c c e e I I n n f f o o r r m m a a t t i i o o n n This function is used to modify names and addresses of devices connected to the Logger3000. The method is as follows: Click "Edit" on the "Device operation" interface, and then "Save" to save the editing operation.
Click "browse" to import an upgrading file, and then click "Confirm upgrade". 9.9 System Setting 9.9.1 SystemTime Setting This function is used to set the system time and time zone of the Logger3000. The method is as follows: step 1 Click "Settings" -> "Time setting" to enter the corresponding interface.
9 Web Interface User Manual 9.9.2 Serial Port Setting This function is used to set serial port parameters of the Logger3000, such as PLC port and COM port (A1B1~A6B6). The parameters include function, baud rate, check bit, stop bit, etc.
Click "Network port" to set network port parameters. • If the access IP is set to "0.0.0.0", any background device with valid IP address can access the Logger3000. If the access IP is set to a specific value, only this background can access the Logger3000.
9 Web Interface User Manual 9.9.6 IEC104 Service Settings This function is used to configure the IEC104 services of the Logger3000. The method is as follows: Click "Settings" -> "IEC104 service settings" to enter the corresponding interface. If the access IP is set to "0.0.0.0", any background device with valid IP address can access the Logger3000.
User Manual 9 Web Interface P P a a r r a a m m e e t t e e r r D D e e s s c c r r i i p p t t i i o o n n R R a a n n g g e e F F i i e e l l d d b b y y t t e e l l e e n n g g t t h h Transmission reason...
Page 54
C C l l o o u u d d s s e e r r v v i i c c e e s s e e t t t t i i n n g g Enable the cloud service setting function if you want to upload the device information collected by the Logger3000 to the iSolarCloud. Otherwise, you may enable or disable the function.
According to the requirements of the grid company, the working status of the inverter forwarded by the Logger3000 must be uploaded to the local background according to the local standards. Therefore, set the country and region to the location where the Logger3000 is installed before using it. The method is as follows: Click "Settings"...
Page 56
9 Web Interface User Manual - - - - E E n n d d...
For more information. refer to "10.3 EMU Setting"。 Data upload function • The Logger3000 can upload the running data of the inverter in the PV system to iSolarCloud. The schematic diagram of the direct-connection networking is as follows:...
In the cascading mode, inverters can be connected to multiple Loggers. The schematic diagram is as follows: The Logger3000 connected to the inverter is slave unit by default; and the Logger3000 connected to the meter and the slave unit is master unit by default.
Page 59
In case of direct-connection networking, set the connection mode • to "Direct mode", and then click "Management" -> "Device operation" to add inverter and meter connected to the Logger3000. In case of cascading networking, set the connection mode to "- •...
SUNGROW shall not be held liable for any damage caused. 10.4 Local Power Regulation The Logger3000 can regulate the power of inverter connected to it. The regulation includes active power regulation and reactive power regulation. The method is as follows: step 1 Click "Power grid scheduling"...
Page 61
User Manual 10 Grid Dispatching step 2 Tick the option "Enable" in the upper left corner and click "Save", to enable the local regulation function. step 3 Select the corresponding local regulation mode, for example, active power regulation and reactive power regulation. table 10-1 Description of active regulation parameters P P a a r r a a m m e e t t e e r r D D e e s s c c r r i i p p t t i i o o n n...
10.5 BDEW According to the BDEW standard, it is necessary to configure a digital input or an analog input to the Logger3000, to achieve the remote grid dispatching function. The method is as follows: step 1 Click "Power grid scheduling" -> "BDEW", to enter the corresponding interface, as shown in the figure below.
Due to the influence of ambient temperature, humidity, dust and vibration, the inner components of the Logger3000 will be aging and worn out. To ensure the system safety and maintain the efficiency of the Logger3000, it is necessary to carry out routine and periodic maintenance.
Check to make sure there is no strong EMC interference device around the Logger3000 Working Check to make sure there is no hot source around the Logger3000. environment Check to make sure there is no corrosive materials around the Logger3000...
SUNGROW with the following information provided: Serial number of the Logger3000, date of manufacture, and software version • Manufacture, type, configuration, and other information of device connected to the •...
Page 66
1. Check the RS485 cable connecting the device and 1. The RS485 cable the Logger3000 and ensure it connecting the device and is not in short circuit, open the Logger3000 is abnormal. circuit, or reverse connection between RS485–A and...
Page 67
User Manual 12 Troubleshooting P P o o s s s s i i b b l l e e c c a a u u s s e e F F a a u u l l t t C C o o r r r r e e c c t t i i v v e e m m e e a a s s u u r r e e 2.
Page 68
12 Troubleshooting User Manual P P o o s s s s i i b b l l e e c c a a u u s s e e F F a a u u l l t t C C o o r r r r e e c c t t i i v v e e m m e e a a s s u u r r e e 5.
Page 69
4. Communication connection to upgrade the inverter again is abnormal. if so. If the fault persists, contact SUNGROW. 1. Log into the Web, and click "Monitoring", to check whether the communication 1. Communication connection status icon is normal, like this is abnormal.
13 FAQ Q1. How many types of communication ports does the Logger3000 support, what are the corresponding ports, and how to set the port parameters? T T y y p p e e P P a a r r a a m m e e t t e e r r s s e e t t t t i i n n g g...
Page 71
User Manual 13 FAQ Logger3000s closer to the Ethernet switch (<100m) are connected to the Ethernet switch by using network cables. Logger3000s relatively far away from the Ethernet switch (>100m) are connected to the Ethernet switch by using routed fiber optic cables. After cable connection, IP address of the multiple Logger3000s should be set to be within the same network segment, without repeated addresses.
14 Appendix A: Technical Data C C o o m m m m u u n n i i c c a a t t i i o o n n Inverter communication RS485 Ethernet / RS485 PC communication Max. Communication Range RS485/Ethernet 1000 m /100 m Interface Design...
15 Appendix B: Related Drawings R R a a c c k k - - m m o o u u n n t t e e d d d d r r a a w w i i n n g g s s W W a a l l l l - - m m o o u u n n t t e e d d d d r r a a w w i i n n g g s s...
16 Appendix C: General Information 16.1 Quality Guarantee SUNGROW shall service or replace the faulty product for free within the warranty period. E E v v i i d d e e n n c c e e Within the warranty period, SUNGROW shall require the customer to present the purchase invoice and date.
Page 75
Serial number of the device • Fault code/name • Brief description of the problem • Australia China (HQ) Sungrow Power Supply Co., Ltd Sungrow Australia Group Pty. Ltd. Hefei Sydney +61 2 9922 1522 +86 551 65327834 service@sungrowpower.com service@sungrowpower.com.au Brazil...
Page 76
SungrowThailand Co., Ltd. Sungrow Ibérica S.L.U. Bangkok Navarra +66891246053 service.spain@sungrow.co service@th.sungrowpower.com Romania Turkey Service Partner - Elerex Sungrow Deutschland GmbH Turkey Istanbul Representative Bureau +40 241762250 Istanbul service.romania@sungrow.co +90 2127318883 service.turkey@sungrow.co U.S.A, Mexico Sungrow Power UK Ltd. Sungrow USA Corporation...
Page 77
Sungrow Power Supply Co., Ltd. Add: No.1699 Xiyou Rd.,New & High Technology Industrial Development Zone, 230088,Hefei, P. R. China. Web: www.sungrowpower.com E-mail: info@sungrow.cn Tel: +86 551 6532 7834 / 6532 7845 Specifications are subject to changes without advance notice.