7 Tag Data Link Functions
7-1-3

Tag Data Link Functions and Specifications

The tag data link and performance specifications of the NJ/NX-series CPU Unit are given below.
Item
Communications type
Setting method
Supported variable
*
Tags
types
1
Maximum number of
words per tag
Maximum number of
tags
Tag
Maximum number of
sets
tags per tag set
Maximum number of
words per tag set
Maximum number of
tag sets
Connections
Connection type
Packet interval (RPI)
Allowed communications
bandwidth per Unit (pps)
*1.
When you specify a specific I/O memory address for a tag for an NX102, NX1P2 or NJ-series CPU Unit,
create a variable with an AT specification for the I/O memory address on the Sysmac Studio, and then
7-6
NX701-£££
NX102-£££
£
£
Standard EtherNet/IP implicit communications (connection-type cyclic commu-
nications)
After you have set tags, tag sets, and connections with the Network Configura-
tor, you must download tag data link parameters to all devices on the
EtherNet/IP network. After the parameters are downloaded, the EtherNet/IP
Units are restarted to start the tag data links.
You can export network variables that you created on the Sysmac Studio to a
CSV file.
You can then import the file to the Network Configurator and assign the net-
work variables to the tags.
You can specify the following network variables as tags.
Global variables
722 words
300 words (600 bytes)
(1,444 bytes)
256
(total of 512 with two ports)
8 (7 when Controller status is included)
722 words
300 words (600 bytes)
(1,444 bytes)
256 (total of
32 (total of 40
512 with two
with two
ports)
*5
ports)
Maximum
Maximum
number of
number of
connections
connections
per unit: 512
per Unit: 64
(256 per port)
(32 per port)
Each connection can be set for 1-to-1 (unicast) or 1-to-N (multicast) communi-
cations.
0.5 to 10,000
1 to 10,000
ms in 0.5-ms
ms in 1-ms
increments
increments
The packet interval can be set separately for each connection.
12,000pps
*6
40,000pps
*6
Note: The
Note: The
heartbeat is
heartbeat and
included.
the CIP Safe-
ty routing are
*7
included.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Specification
NJ501-££££/NJ301-£££
£/NJ101-££££
NX1P2-£££
££££
Unit version
1.00 to 1.02
*2*3
*4
256
32
Maximum number of connections per Unit: 32
2 to 10,000
10 to 10,000
ms in 1-ms
ms in 1-ms
increments
increments
3,000 pps
1,000 pps
Note: The heartbeat is included.
Unit version
1.03 or later
1 to 10,000
ms in 1-ms in-
crements
3,000 pps