2 Installing Ethernet Networks
NJ-series CPU Unit
10Base-T
Connect the shield at both ends
or
Connect the shield only at the Ethernet
switch side
*1.
For NX701 CPU Units only.
• 10Base-T or 100Base-TX
Connect the cable shields to the connector hoods as described in either (1) or (2) below.
1. Connecting the shields at both ends of the cable
Connect the shields to the connector hoods at both ends of the cables.
Ethernet switches
Connector
GR
terminal
2. Connecting the shields only at the Ethernet switch side
Connect the shields to the connector hoods only at the Ethernet switch side.
• For an NX-series CPU Unit, a clamp core must be attached to the end of the cable at the
EtherNet/IP port side. For a recommended clamp core and attachment methods, refer to
Recommended Clamp Core and Attachment Method on page 2-10.
To comply with EMC standards, it is mandatory that a clamp core be attached when con-
necting the shield to the connector hood only at the Ethernet switch side.
• For an NJ-series CPU Unit, it is not necessary to attach a clamp core.
2-8
100Base-TX
Connector
Connector
STP
(Shield)
Built-in
EtherNet/IP port
STP
(Shield)
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
NX-series CPU Unit
10Base-T
100Base-TX
Connect the shield at both ends
or
Connect the shield only at the Ethernet
switch side. A clamp core must be at-
tached to the EtherNet/IP port side of
the cable.
Connect shield to connector hood
Built-in EtherNet/IP port
Power Supply
on NX-series CPU Unit
Unit
Connector
GR
terminal
Built-in EtherNet/IP port
Power Supply
on NJ-series CPU Unit
Unit
Connector
GR
terminal
1000Base-T
*1
Connect the shield
at both ends