Appendices
• Setting for Tag Sets
Tag Set Name
Size (Byte)
Instance ID
Controller Status
• Setting for Tags
Tag Name
Bit Selection
Size (Byte)
Size (Bit)
Output at Fatal Error
Setting Connections for the Originator Device
After the tag set registration, set the connection settings for transferring data using the EtherNet/IP
connections.
Make the connection settings in the originator device (i.e., Controller 1 in this example) only.
Register the tag and tag set for Controller 2 (Target device) before setting the connection settings as
described in this example.
Refer to Registering the Tag and Tag Set for the Target Device on page A-22 for the operations for
registering tags and tag sets.
A-14
Name
Enter the tag set name.
You can change the names as required.
Gives the total size of the tag in bytes.
Gives the instance ID.
Auto
IN_{min}...IN_{max}
{min} represents the minimum number of Produced Assembly identifica-
tion numbers recorded in the EDS files for the relevant devices.
{max} represents the maximum number of Produced Assembly identifica-
tion numbers recorded in the EDS files for the relevant devices.
Specify whether to include the Controller status in the tag set.
Name
Enter the tag name.
Specify the tag name that matches one of the registered network variable
names in the Controller.
Specify whether to set the tag data size in bits.
Selected: Set the size in bits.
Not selected: Set the size in bytes.
Gives the size of the tag in bytes.
Gives the size of the tag in bits.
Specify whether to clear the output data or continue to send it when a ma-
jor fault level Controller error occurs in the Controller.
Retained
Cleared
Item
Item
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)