Omron NJ Series User Manual page 123

Machine automation controller, cpu unit built-in ethernet/ip port
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Variable name
_EIP_IPRTblErr
Meaning
IP Route Table Error
Function
NX-series CPU Units: Indicates that the default gateway settings or IP router table settings are incorrect. Or, a
read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
NJ-series CPU Units: Indicates that the IP router table or hosts settings are incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
Variable name
_EIP_IdentityErr
Meaning
Identity Error
Function
NX-series CPU Units: Indicates that the identity information for CIP communications 1 (which you cannot over-
write) is incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
NJ-series CPU Units: Indicates that the identity information (which you cannot overwrite) is incorrect. Or, a read
operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
Variable name
_EIP1_IdentityErr
Meaning
CIP Communications1 Identity Error
Function
Indicates that the identity information for CIP communications 1 (which you cannot overwrite) is incorrect. Or, a
read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Note You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
Variable name
_EIP2_IdentityErr
Meaning
CIP Communications2 Identity Error
Function
Indicates that the identity information for CIP communications 2 (which you cannot overwrite) is incorrect. Or, a
read operation failed.
TRUE: Setting incorrect or read failed.
FALSE: Normal
Note You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
3 System-defined Variables Related to the Built-in EtherNet/IP Port
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
3
3-45