Data Link Specifications - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

What Are Data Links?
5-1-1

Data Link Specifications

Note
92
Item
Number of
62 max., 2 min. (See note 1 and 2.)
data link
nodes
Number of
Number of send words per node (total for area 1 and 2):
data link
4,000 words max. (model numbers ending in CLK13 and CLK53)
words
1,000 words max. (all other Units and Boards)
Number of send/receive words per node (total of Area 1 and Area 2):
CS:
CVM1/CV:
IBM or compatible: Manual setting: 62,000 max. (See note 1.)
Allocation of
Manual
data link
setting
areas
Automatic
setting
equality
layout
Automatic
setting 1:N
allocations
1. In systems that combine Optical Bus Controller Link Units/Boards (model
numbers ending with CLK11) with other Units/Boards, the max. number of
nodes and words are as follows:
Method
Manual
Optical Bus Units/Boards:
Up to 32 nodes (with node addresses 1 to 32) can be data linked
and the max. number of data link words is 32,000 words/node.
Automatic
All Units/Boards:
Up to 32 nodes (with node addresses 1 to 32) can be data linked
and the max. number of data link words is 32,000 words/node.
2. If Controller Link Units are used in duplex operation, the maximum number
of active nodes is equal to the following:
62 − Number of standby Units
Description
12,000 max. (pre-Ver. 1.2)
20,000 max. (unit Ver. 1.2 or later)
8,000 max.
Automatic setting: 8,000 max.
Area 1, 2: Bit area (CIO and LR Areas)
Data Memory (DM and EM Areas)
Unit Ver. 1.2 or later: Area 1 and Area 2 can be set in the
same memory area.
Pre-Ver. 1.2: Area 1 and Area 2 cannot be set in the same
memory area.
Area 1: CIO or LR Area
Area 2: Data Memory (DM and EM Areas)
Area 1, 2: Bit area (CIO and LR Areas)
Data Memory (DM and EM Areas)
Specification
Section 5-1

Advertisement

Table of Contents
loading