Goodrive20-EU Series VFD
Function
Name
code
Deceleration
time for
P08.21
emergency
stop
Delay to enter
P08.22
the sleep state
Preset voltage
P08.23
and frequency
Enabling
energy
P08.24
consumption
braking stop
Setting
P08.25
counting value
Reference
P08.26
counting value
Setting running
P08.27
time
0.0–6553.5s
0.0 indicates coasting to stop.
0.0–3600.0s
It indicates the delay to enter the sleep state, and
it is valid only when ones place of P01.19 is set
to 2.
0: 230 V preset voltage and 50Hz preset frequency
1: 220 V preset voltage and 60Hz preset frequency
2: 400 V preset voltage and 50Hz preset frequency
3: 460 V preset voltage and 60Hz preset frequency
0: Disable
1: Enable
The counter works by the input pulse signals of
the HDI terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the
signal of "fixed counting number arrival" and the
counter go on working; when the counter
achieves a setting number, the multi-function
output terminals will output the signal of "setting
counting number arrival", the counter will clear all
numbers and stop to recount before the next
pulse.
The setting counting value P08.26 should be no
more than the setting counting value P08.25.
The function is illustrated as below:
S terminal
Y1
RO1, RO2
Setting range of P08.25: P08.26–65535
Setting range of P08.26: 0–P08.25
Pre-set running time of the VFD. When the
accumulative running time achieves the set time,
Description
Reach the designated
-77-
Function parameters
Default Modify
0.0s
2.0s
2
1
0
0
Reach the set
counting value
counting value
0m