INVT Goodrive20-EU Series Operation Manual page 59

Vfd
Hide thumbs Also See for Goodrive20-EU Series:
Table of Contents

Advertisement

Goodrive20-EU Series VFD
Function
Name
code
P04.01
Torque boost
Torque boost
P04.02
end
V/F frequency
P04.03
point 1
V/F voltage
P04.04
point 1
V/F frequency
P04.05
point 2
Output voltage
Linear type
Square type
Torque boost to the output voltage for the
features of low frequency torque. P04.01 is for
the max. output voltage V
P04.02 defines the percentage of closing
frequency of manual torque to f
Torque boost should be selected according to
the load. The bigger the load is, the bigger the
torque is. Too big torque boost is inappropriate
because the motor will run with over magnetic,
and the current of the VFD will increase to add
the temperature of the VFD and decrease the
efficiency.
When the torque boost is set to 0.0%, the VFD is
automatic torque boost.
Torque boost threshold: below this frequency
point, the torque boost is valid, but over this
frequency point, the torque boost is invalid.
Output voltage
v
b
v
boost
Setting range of P04.01: 0.0%: (automatic)
0.1%–10.0%
Setting range of P04.02: 0.0%–50.0%
100.0%
V
b
V3
V2
V1
Description
Torque step-down V/F curve (1.3 order)
Torque step-down V/F curve (1.7 order)
Torque step-down V/F curve (2.0 order)
Output frequency
.
b
.
b
Output
frequency
f
f
Cut-off
Output voltage
Output
frequency
f1
f2
f3
f
b
-54-
Function parameters
Default Modify
0.0%
20.0%
0.00Hz
0.0%
0.00Hz