Goodrive20-EU Series VFD
Function
Name
code
Communication
P14.04
overtime fault
time
Transmission
P14.05
error
processing
Communication
P14.06
processing
action selection
User-defined
address for
P14.07
running
commands
User-defined
address for
P14.08
frequency
setting
the system processing time, if the answer delay
is longer than the system processing time, then
after the system deal with the data, waits until
achieving the answer delay time to send the data
to the upper monitor.
0.0 (invalid), 0.1–60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds
the
communication
system will report "485 communication faults"
(CE).
0: Alarm and stop freely
1: No alarm and continue running
2: No alarm and stop as per the stop mode (only
under communication control mode)
3: No alarm and stop as per the stop mode
(under all control modes)
0x000–0x111
Ones place: Responding to write operations
0: Yes
1: No
Tens place: Communication encryption
0: Disabled
1: Enabled
Hundreds place: User-defined communication
command address
0: Disabled
1: Enabled
0x0000–0xffff
0x0000–0xffff
Description
overtime,
-97-
Function parameters
Default Modify
0.0s
the
0
0x000
0x1000
0x2000