P05 Group Input Terminals - INVT Goodrive20-EU Series Operation Manual

Vfd
Hide thumbs Also See for Goodrive20-EU Series:
Table of Contents

Advertisement

Goodrive20-EU Series VFD
Function
Name
code
Flux
weakening
P04.33
coefficient in
constant
power zone

P05 group Input terminals

Function
Name
code
HDI input
P05.00
selection
S1 terminal
P05.01
function
selection
S2 terminal
P05.02
function
selection
S3 terminal
P05.03
function
selection
S4 terminal
P05.04
function
selection
Vmax
Vset
Vmin
Adjust the output voltage of the VFD in SVPWM
mode during flux weakening.
Note: Invalid in the constant torque mode.
Output Voltage
V
out
V
b
Setting range of P04.33: 1.00–1.30
0: HDI is high pulse input. See P05.50–P05.54
1: HDI is switch input
Note: S1–S4, HDI are the upper terminals on the
control board and P05.12 can be used to set the
function of S5–S8
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: Tri-linear running control
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
Description
t1=P04.29
t2=P04.30
t1
t2
T
(P04.33-1.00)*Vb
Output frequency
f
2f
b
b
Description
-57-
Function parameters
Default Modify
1.00
Default Modify
0
1
4
7
0

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive20-EU Series and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF