Emerson Rosemount 2230 Reference Manual page 117

Graphical field display
Hide thumbs Also See for Rosemount 2230:
Table of Contents

Advertisement

Reference Manual
00809-0100-2230
Table 5-11: Recommended Actions for Field Diagnostics Alerts
Alert Type
Failure
Out of
Specification
Function
Check
Rosemount 2230 Graphical Field Display
Description
Software Failure
Database Error
Electronics failure - Main
Board
Electronics failure - FF I/O
Board
Memory Failure - FF I/O Board
Internal Communication
Failure
Internal Temperature Out of
Limits
Invalid Model Code
MAO Fault State Mode
enabled
Check Function
Service and troubleshooting
Recommended Action
1. Restart communication.
2. Load default database to the device and
reconfigure the device.
3. Contact Rosemount Tank Gauging Service
Department.
1. Restart communication.
2. Load default database to the device.
3. Reconfigure the device.
Replace the device.
Replace the device.
1. Restart communication.
2. If error persists it may indicate a faulty
memory chip. Replace the device.
1. Restart communication.
2. Replace the device.
Check ambient temperature at installation site.
Contact Emerson Automation Solutions /
Rosemount Tank Gauging service department.
One or several Multiple Analog Output (MAO)
blocks are configured with fault-state mode
enabled. With this configuration, the output on
the display will show the fault-state data not the
actual data from the connected devices.
Turn fault state mode off in MAO block.
One or more transducer blocks are in Out of
Service mode. Return transducer block to Auto
mode.
March 2021
117