Troubleshooting

5.3.1
Troubleshooting the Rosemount 2230
Table 5-3
most common operating problems.
Table 5-3: Troubleshooting Chart for the Rosemount 2230 Display
Symptom
No communication
with the Rosemount
2230
Rosemount 2230 Graphical Field Display
provides summarized maintenance and troubleshooting suggestions for the
Possible cause
Wiring
Cables are too long
Hardware failure
Service and troubleshooting
Action
Check that wires are properly connected to
the terminals
Check for dirty or defective terminals
Check wire insulation for possible short
circuits to ground
Check that there are no multiple shield
grounding points
Check that the cable shield is grounded at
the power supply end only
Check that the cable shield is continuous
throughout the fieldbus network
Check that the shield inside the instrument
housing does not come into contact with
the housing
Check that there is no water in conduits
Use shielded twisted pair wiring
Connect wiring with drip loops
Check that the input voltage on the device
terminal is 9 V or more
Check the Rosemount 2230 if other
devices such as the Rosemount 2410 Tank
Hub are detected by the host system. In a
F
Fieldbus system you can
OUNDATION
check the Device Live List to confirm that
the host can detect other devices.
Contact Emerson Automation Solutions/
Rosemount TankGauging service
department
March 2021
103