Reference Manual
00809-0100-2230
Table C-7: Multiple Analog Output Block Parameters
Index
Number
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Rosemount 2230 Graphical Field Display
Parameter
IN_8
MO_OPTS
FSTATE_TIME
FSTATE_VAL1
FSTATE_VAL2
FSTATE_VAL3
FSTATE_VAL4
FSTATE_VAL5
FSTATE_VAL6
FSTATE_VAL7
FSTATE_VAL8
FSTATE_STATUS
UPDATE_EVT
BLOCK_ALM
F
Fieldbus Block Information
OUNDATION
(continued)
Description
Numbered input parameter for multiple output
function blocks
Options that the user may select to alter multiple
output block processing. In case a Fault State option
is set, the 2230 will send a Field Diagnostic alert.
The preset analog value to use when failure occurs in
IN_1. Ignored if the "Fault state to value 1" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_2. Ignored if the "Fault state to value 2" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_3. Ignored if the "Fault state to value 3" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_4. Ignored if the "Fault state to value 4" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_5. Ignored if the "Fault state to value 5" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_6. Ignored if the "Fault state to value 6" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_7. Ignored if the "Fault state to value 7" in the
MO_OPTS parameter is false.
The preset analog value to use when failure occurs in
IN_8. Ignored if the "Fault state to value 8" in the
MO_OPTS parameter is false.
Shows which points are in fault state.
This alert is generated by any change to the static
data.
The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as
the Unreported status is cleared by the alert
reporting task, another block alert may be reported
without clearing the Active status, if the subcode has
changed.
March 2021
173