Configuration and operation
March 2021
Related information
Alarm priority
Function check alerts
A Function Check alert indicates that the device is temporary non-valid due to some
activities, for example maintenance, on the device.
There are five parameters associated with Function Check alerts, they are described below.
FD_CHECK_MAP
The FD_CHECK_MAP parameter contains a list of informative conditions that do not have
a direct impact on the primary functions of the device. Below is a list of the conditions:
1. Check function
FD_CHECK_MASK
The FD_CHECK_MASK parameter will mask any of the failed conditions listed in
FD_CHECK_MAP. A bit on means the condition is masked out from alarming and being
broadcast to the host through the alarm parameter.
FD_CHECK_PRI
FD_CHECK_PRI designates the alarming priority of the FD_CHECK_ALM. The default is 0
and the recommended values are 1 or 2.
FD_CHECK_ACTIVE
The FD_CHECK_ACTIVE parameter displays which of the conditions is active.
FD_CHECK_ALM
FD_CHECK_ALM is an alarm indicating that the device output is temporary invalid due to
on-going work on the device.
Related information
Alarm priority
4.13.4
Recommended actions for alerts
The RECOMMENDED_ACTION parameter displays a text string that will give a
recommended course of action to take based on which type and which specific event of
the alerts is active.
Related information
Recommended actions