4.13.5
Alarm priority
Alarms are grouped into five levels of priority:
Table 4-8: Alarm Levels of Priority
Priority number
0
1
2
3-7
8-15
Rosemount 2230 Graphical Field Display
Priority description
The priority of an alarm condition changes to 0 after the condition that
caused the alarm is corrected.
An alarm condition with a priority of 1 is recognized by the system, but is
not reported to the operator.
An alarm condition with a priority of 2 is reported to the operator, but
does not require operator attention (such as diagnostics and system
alerts).
Alarm conditions of priority 3 to 7 are advisory alarms of increasing
priority.
Alarm conditions of priority 8 to 15 are critical alarms of increasing
priority.
Configuration and operation
March 2021
83