Start proof test
It is possible to initiate a pre-configured proof test of a Rosemount
is a short introduction how to perform a proof test. See the
Rosemount 2410 Safety Manual
Prerequisites
Note that the relay and/or analog output is active during the proof test.
Procedure
1. In the Display Tank view, select Menu to open the Main Menu view.
2. Select the Service option.
3. Select Start proof test.
4. Enter the password. Note that default password is "000".
5. Choose the desired tank.
6. Select OK to continue and follow the instructions on the display.
Rosemount 2230 Graphical Field Display
for a complete instruction.