00809-0100-2230
7. Proceed with configuration of Multiple Analog Output (MAO) blocks by pressing the
8. Configure all inputs that are used for the MAO Block.
Related information
Viewing device status in AMS Device Manager
Multiple Analog Output blocks
Multiple analog output block window
Multiple analog output block window
The Multiple Analog Output Block window lets you map tanks and tank parameters from the
Multiple Analog Output (MAO) block inputs 1 - 8 to the tanks and tank parameters in the
Rosemount 2230 transducer block. This configuration is required in order to make the
field device parameters available on the display output.
Figure 4-16: Multiple Analog Output Block Window
Note that MAO Block 1 to MAO Block 4 refer to index number 1400 to 1700 (MAO_1400 -
MAO_1700).
For each tank you may not configure more than one Tank Parameter of a certain type. This
means that for each tank you may specify one Level, one Liquid Temperature, etc.
Rosemount 2230 Graphical Field Display
appropriate button; Multiple Analog Output Block #.
Configuration and operation
March 2021